SFCP II RAIL
			
		
	TECHNICAL SPECIFICATIONS
- Developed and designed according to DIN 14497 (small extinguishing systems) based on EN 12094-1
 - Fault and alarm identification directly via LEDs on the control panel
 - Power supply via wide range input from 11 to 32 V DC (optional battery emergency operation)
 - Housing protection class IP68
 - Adjustable operating mode via DIP switch: manual, 1- or 2-line dependency for detection, alarm and extinguishing output
 - Manual triggering (double buttons to avoid unintentional false triggering) and extinguishing delay (“Hold”) also possible at the control panel of the control unit
 - Two monitored limit alarm lines for connecting up to 4 conventional smoke detectors, multi-sensor detectors, linear heat detectors, rod heat detectors, flame detectors each
 - 1 monitored alarm line for external manual control device according to EN 12094-1
 - 1 monitored limit value signal line for external extinguishing delay button (stop button)
 - 1 output external alarm device
 - 1 monitored extinguishing agent output (optimized for monitored control of max. 4 Stat-X aerosol extinguishing cartridges)
 - 3 configurable, potential-free alarm outputs with change-over contact 30 V DC / 1 A load (sum fault, pre-alarm, main alarm)
 - Operating voltage: 11 – 32 V DC
 - Quiescent current nominal: 41 mA
 - Alarm current: 1 to 4 A (short-time) in connection with an aerosol extinguisher (4 extinguishers, depending on the dimension)
 - dimensions: 120 x 80 x 57 mm
 - weight: 99 g
 - Material housing: PC (UL 94 / V0)
 
STANDARDS:
- EU Directive 2014/30/EU;
 - FCC compliance according to EN 50130-4/2011
 - FCC CFR 47, part 15/2013
 - EN 61000 (parts 4-2 to 4-8)
 - EN 61000 (part 6-3 / 2012)
 - EN 50155, EN 50121-3, EN 60068, EN 61373