TECHNICAL SPECIFICATIONS

  • Developed and designed according to DIN 14497 (small extinguishing systems) based on EN 12094-1
  • Fault and alarm identification directly via LEDs on the control panel
  • Power supply via wide range input from 11 to 32 V DC (optional battery emergency operation)
  • Housing protection class IP68
  • Adjustable operating mode via DIP switch: manual, 1- or 2-line dependency for detection, alarm and extinguishing output
  • Manual triggering (double buttons to avoid unintentional false triggering) and extinguishing delay (“Hold”) also possible at the control panel of the control unit
  • Two monitored limit alarm lines for connecting up to 4 conventional smoke detectors, multi-sensor detectors, linear heat detectors, rod heat detectors, flame detectors each
  • 1 monitored alarm line for external manual control device according to EN 12094-1
  • 1 monitored limit value signal line for external extinguishing delay button (stop button)
  • 1 output external alarm device
  • 1 monitored extinguishing agent output (optimized for monitored control of max. 4 Stat-X aerosol extinguishing cartridges)
  • 3 configurable, potential-free alarm outputs with change-over contact 30 V DC / 1 A load (sum fault, pre-alarm, main alarm)
  • Operating voltage: 11 – 32 V DC
  • Quiescent current nominal: 41 mA
  • Alarm current: 1 to 4 A (short-time) in connection with an aerosol extinguisher (4 extinguishers, depending on the dimension)
  • dimensions: 120 x 80 x 57 mm
  • weight: 99 g
  • Material housing: PC (UL 94 / V0)

 

STANDARDS:

  • EU Directive 2014/30/EU;
  • FCC compliance according to EN 50130-4/2011
  • FCC CFR 47, part 15/2013
  • EN 61000 (parts 4-2 to 4-8)
  • EN 61000 (part 6-3 / 2012)
  • EN 50155, EN 50121-3, EN 60068, EN 61373